Steve,
Looks like George beat me to it but I had the post already written so, here’s my take on it and I’m afraid I might get a bit wordy here. Under Article 680 Part IV Spas & Hot Tubs of the NEC, we look in section 680.42 Outdoor Installations, which says: “outdoor installations shall comply with parts I & II of this article”. Part II of Article 680 deals with permanently installed pools which includes equipotential bonding per 680.26(b)(2) for bonding perimeter surfaces extending 3’ from the pool or in this case, hot tub. Now that we know we have do it the question is can we use a steel reinforcing mat, like the type used in sidewalks, in direct contact with the earth and can this be used as the equipotential grid under the perimeter in the pool. My answer is no. In the last code cycle most electrical inspectors were allowing the a steel reinforcing mat to be used as an equipotential grid if it was not in direct contact with the soil but embedded in the concrete. This was being allowed even though it was never really approved in Article 680. The proper way to do it was either with re-rod or the welded copper mat that is now required and described in section 680.26(B)(1)(b). The problem with using just a steel mat is that if it is in direct contact with the soil and not in the concrete is that it will be destroyed by rust. Once the inspector left the job he had no way of knowing if the mesh was installed properly in the pour. In the 2008 NEC another option was given to accomplish the bonding of the perimeter surfaces and it’s reletivly inexpensive and accomplishes what it is intended to do. Section 680.26(B)(2)(b) reads: (b) Alternate Means. Where structural reinforcing steel is not available or is encapsulated in a nonconductive compound, a copper conductor(s) shall be utilized where the following requirements are met:
(1) At least one minimum 8 AWG bare solid copper conductor shall be provided.
(2) The conductors shall follow the contour of the perimeter surface.
(3) Only listed splices shall be permitted.
(4) The required conductor shall be 450 to 600 mm (18 to 24 in.) from the inside walls of the pool.
(5) The required conductor shall be secured within or under the perimeter surface 100 mm to 150 mm (4 in. to 6 in.) below the subgrade.
This new option should be the method used both for both paved and unpaved surfaces such as the pavers you have described.
Hope that helps……..Tony