2017 NEC Art. 210.63
Heating, Air conditioning, and Refrigeration Equipment Outlet.
The required receptacle outlet shall not be connected to the load side of the equipment disconnecting means.
There are disconnects equipped with built-in GFI receptacles.
Their purpose may not be targeted at A/C, but they are in use
for A/C disconnects.
HVAC contractors are pulling power for these receptacles from the line
Side of the A/C disconnect. They explain supply houses are informing.
them this meets code compliance. This is because the power is taken.
prior to the disconnect fuses on the line side, not the load side.
Using this GFI built-in outlet and the line side of the disconnect would
require the following. A 3-conductor with ground. Disconnect terminals.
Approved and marked for more than one conductor per terminal.
Would the code missing the word line and load side of the equipment give
permission for allowing line side receptacle power?
I have not seen a cut sheet on these disconnects.
I do not see this as a code-compliant way to meet the intent of the
2017 NEC Art. 210.63 Please supply your thoughts on this.
It is so great to have our own discussion forum up and running again.
Thank you all.