Conductor size in Commercial Building

  • 24 Feb 2013 12:41 PM
    Message # 1225215
    Anonymous
    Is there any place in the 2008 NEC that requires a minimum size #12 AWG conductors in a commercial Building?
  • 25 Feb 2013 5:34 AM
    Reply # 1225658 on 1225215
    Mr. Brunning there is nothing in the 2008 NEC that says you must use a minimum #12 conductor. There used to be a rule that the RECI had in their RECI manual which was approved by the State that said minimum #12 conductor in commercial wiring. That is long since gone away. There is alway a possibility that the plans may be asking for #12 wire, in which case the inspector would be expecting #12 wire. 